The basis of design for estimating a heat load is similar for precision air conditioning and comfort air conditioning. However the following points must be carefully considered and taken into account while making the equipment selection:
a) Inside conditions of temperature and humidity: The recommended inside condition by ASHRAE is 22°C±1°C db and 50% ±5%RH.
b) Outside conditions: Suitable derating of equipment capacity must be considered based on a condensing temperature which is normally 20°F higher than ambient temperature and varies with the ambient temperature.
c) Equipment selection must satisfy the heat load and air quantity requirements. Precision air conditioners have airflow in excess of 550 cfm per ton.
d) Standby requirement: having calculated the heat load, the next step is to decide the capacity and number of air conditioning units to be selected from the standard models available from most manufacturers and accordingly determine the capacity of the standby unit. As an example, if the heat load works out to 75 Kw, one can select three units of 25 Kw as operational plus one unit to work as a standby (commonly referred to as n = 3 + 1) or select two units of 37.5 Kw as operational plus one unit as a standby (referred to as n = 2 + 1). The criticalness of the air-cond area, total price of each selection and the physical constraints at the installation site will finally determine the best choice.
Heat loads should account for the following internal loads in the Server room:
- equipment loads are normally assumed on the basis of density per sq.ft and it is all sensible heat. It can varies from 15 Watt per sq.ft. for scarcely populated server rack with low heat generating server to 200 Watt Btu/hr per sq.ft. for densely populated server room with high heat generating servers. The most accurate heat estimation is to get the heat rejection load of the IT equipment to be installed. Diversity factor for equipment load is approximately 60-80%.
- occupancy levels are minimum, normally 2 or 3 persons.
- lighting loads are normally considered at 1.5 watts per sq.ft.